Short Circuit Current Ratings & Solid State Relays
Click here to download PDF

For additional information:

AMERICAS

United States and Canada
2320 Paseo de las Americas, Suite 201, San Diego, CA 92154
sales@crydom.com

Sales Support:
(877) 502 5500
Technical Support:
(877) 702 7700
Fax (619) 710 8540

Brazil
Tel: +55 (11) 3026 9008
Fax: +55 (11) 3026 9009

Other American Countries
Sales Support:
(877) 502 5500
Technical Support:
(877) 702 7700
Fax (619) 710 8540

EUROPE

United Kingdom
Tel: +44 (0) 1202 606030
sales-europe@crydom.com
Fax: +44 (0) 1202 606035

Germany
Tel: +49 (0) 180 3000 506

Italy
Tel: +39 02 66599260
Fax: +39 02 66599268

France
Tel: 0 810 123 963
Fax: 0 810 057 605

ASIA

China
Tel: +86 (21) 2401 7766
Fax: +86 (21) 6249 0701
sales-cn@crydom.com

Taiwan
Tel: +886 2 8751 6388
Fax: +886 2 2657 8725
sales-tw@crydom.com

India
Tel: +91 (80) 4113 2204/05
Fax: +91 (80) 4113 2206

OTHER REGIONS

Tel: +44 (0) 1202 606030
Fax: +44 (0) 1202 606035

By Dr. Oscar Montero, Crydom, Inc.
Global Technical Center


 

New Challenges for Industrial Panel Builders
The 2005 National Electrical Code (more information) now requires most control panels to be marked with their short-circuit current rating (SCCR). This change affects all industrial control panels (409.110), industrial machinery panels (670.3(A)), and non-residential HVAC equipment rated greater than 60A (440.4(B)). Furthermore, all industrial control panels listed to UL508A must be marked with their SCCR. Supplement SB in UL508A, which became effective on April 1, 2006, is referenced by the NEC as an approved method for establishing the SCCR of a panel.

As with most every change to the NEC, safety is the primary concern of this new requirement. Under abnormal operating conditions, such as an electrical fault, a control panel may be subjected to thousands of amperes of let-through current before any protective device(s) inside the panel clears the fault. Such an event may cause severe damage to power components and electrical wiring, which can compromise the integrity of the Panel and result in injury to nearby personnel.

Proper matching between the maximum available current from the power supply and the SCCR for the panel is fundamental to ensure safety. From the Panel users point of view, Panels with a higher SCCR allows them the flexibility to connect their Panel to electrical systems with different available currents. From the Panel builder’s point of view, establishing this higher SCCR may represent significant challenges and additional costs.

Establishing the SCCR for Control Panels
Even though supplement SB from UL508A defines how the SCCR for an Industrial Panel is established, determining the Panel’s actual SCCR may not be so straightforward. The simplest method to obtain the Panel’s rating is by analyzing the individual power components in each branch of the circuit. The component with the lowest rating determines the SCCR for the entire branch. Subsequently, the branch with the lowest rating determines the SCCR for the entire panel.

Text Box: Typical Components found in a branch circuit of an industrial control panel:    Circuit Breakers	SSRs  Contactors		Drives  Motor Controllers	Fuses  NEMA Contactors	Transformers  Terminal Blocks	Receptacles  Meter Sockets		Switch Units

Despite the fact that the SCCR rating for SSRs was not available in the past (nor was such a rating required) it is obvious from the above example that this is a critical part of determining the rating for the entire panel. Per UL508A supplement SB, components that do not have such a rating are given one based upon their specific category. SSRs, which do not have a specific category, are considered to fall under “Switches”, “Switch Units”, or “Motor Controller, 0-50HP”. The rating for unmarked components in these categories is 5kA, and the use of such component in a branch circuit effectively reduces the entire panel to the same rating.

  

It must be realized that any rating from this table is subject to meeting what UL defines as conditions of acceptability. It is strongly recommended to check with UL about those conditions for any unmarked component that may be included in the Panel. Moreover, it should be noticed that the rating assigned to the SSR may have an impact on determining the rating for the whole Panel, as will any other power component inside the Panel.

Establishing the SCCR for Solid-State Relays
Per UL508A, short-circuit current ratings can be conveniently established for individual power components, or for combination of power components, or for the Control Panel as a whole. Crydom has elected to test a combination of SSRs with protective devices (fuses initially) in order to meet the conditions of acceptability necessary to assign the standard 5kA rating to the combination. However, most Crydom customers desire a SCCR rating higher than 5kA for their panel in order to be more competitive in the market. For this reason, Crydom is undertaking a series of tests in order to significantly increase the UL approved SCCR ratings for their relays.

The tricky part is selecting the right fuse for not only the application, but also for the desired SCCR rating for the combination. It is understood that under sizing the fuse may compromise performance, while over sizing the fuse may impact the safety of the Panel.  Not to mention add unnecessary cost.  To further complicate the issue, fuses of the same physical size may have different current ratings (i.e. a 60A fuse is the same physical size as a 45A fuse). This is a significant UL concern, as field service technicians could easily replace a fuse with one of identical size but having a higher current rating. Such an error could potentially result it damage to the relay, the load, or nearby personnel.

Therefore, UL requires that the relay-fuse combination be tested with an “umbrella fuse”. That is, the fuse used in the combination must have the highest possible current rating available for that particular fuse package. Since UL approval with a rated fuse covers all fuse ratings up to that value, the “umbrella fuse” method adequately addresses this concern. Crydom’s test plan involves multiple relays of different load-current ratings in combination with the highest possible “umbrella fuse” combination. This not only meets UL’s safety requirements, but also provides panel builders with flexibility in selecting the right relay for their application and their specific SCCR requirements.

hands

Similar to fuses, solid-state relay manufacturers tend to follow a typical industry-standard footprint. However, unlike fuses, each manufacturer’s relays may have significant design differences that affect thermal performance, power dissipation, mechanical stress/fatigue, etc. Therefore, the “umbrella” concept does not apply in the same manner as it does for fuses. So simply substituting one relay with an “equivalent” relay from another manufacturer will not likely result in an equivalent short-circuit current rating.

It should be remembered that SCCR is strongly related to safety, and therefore great caution must be used when changing solid-state relays in control panel.

Who Should be Concerned Over SCCR?
While the new NEC code focuses primarily on the North American market, Panel Builders selling outside of the US may also be affected by the change. Any panel requiring UL Listing, regardless of its final destination, must be marked with a SCCR. In addition, some regions outside of the US may enforce NEC 2005 as an additional safety measure for local installations. Panels in such locations must also have their SCCR clearly marked.

To add to the confusion, some states in the US have not yet adopted NEC 2005. Therefore, they do not yet require the SCCR marking on panels. However, as stated above, a UL Listed panel installed in that particular state must have an approved SCCR, regardless of the state’s regional requirements.

SCCR for Crydom Solid-State Relays
To date, testing for selected combinations of solid-state relays and fuses performed in an UL approved Schneider Electric Laboratory and witnessed by an UL representative has yielded the results shown in the table(s) below. Current and potential customers of Crydom solid-state relays should note the following:

  • Equivalent relays from different manufacturers may not have similar SCCR. Caution is advised when relays are rated in combination with protective devices.
  • The following table(s) contains both UL approved and manufacturer approved relay/fuse combinations. The manufacturer approved combinations are highlighted / italicized. The table(s) also contains generic and specific fuse information. Panel builders can use the generic information in their manufacturing procedure. For example, generic information is when protected by a 30Amp Class J Fuse. In these cases, it is allowed to use fuses of the same class with lower ratings.

Class J Fuses

  
  • Data for a specific manufacturers fuse (i.e. “when protected by a AJT80 Class J Fuse") was obtained in a manner identical to the procedure for generic information (i.e. “when protected by a30A Class J Fuse”). As with the generic evaluation, the specific testing was also witnessed by a UL representative. However, UL does not allow for a SSR to be marked with a specific manufacturers fuse. Regardless, the information remains valuable, as it may be used only as a reference to help panel builders better understand the limits of the branch where the specific relay-fuse combination is located. This information will help in determining the panels overall SCCR in cases where the panel is tested as a complete system.
  • Additional helpful information can be found at Schneider Electric NEC409/UL508 Support Website and Crydom Technical Support.
  • Please contact your Crydom sales representative if you require official information regarding a SSR’s rating.

Crydom Solid-State Relay Short-Circuit Current Ratings (SCCR)*

Type

Product Family

Suitable for use in a circuit capable of delivering not more than:
5kA @ 600Vrms (symmetrical)
100kA @ 600Vrms (symmetrical)
Panel Mount SSR
H12 Series 25A Solid-State Relays,
followed by D/CD/WD, followed by 4825
Additional Products Covered:
Series 1 (240/480Vac), H10, and HA/HD relays of the same ratings and construction are represented by Series H12 

When protected by;
10Amp Class J fuse
OR
10Amp Class CC fuse
ul
UL - E116949, Vol. 2

When protected by;
30Amp Class J fuse
OR
30Amp Class CC fuse
ul
UL - E116949, Vol. 2
H12 Series 50A Solid-State Relays,
followed by D/CD/WD, followed by 4850
Additional Products Covered:
Series 1 (240/480Vac), H10, and HA/HD relays of the same ratings and construction are represented by Series H12 
When protected by;
30Amp Class J fuse
OR
30Amp Class CC fuse
ul
UL - E116949, Vol. 2
When protected by;
60Amp Class J fuse
OR
30Amp Class CC fuse
ul
UL - E116949, Vol. 2
CWD4850 / CWA4850
When protected by;
30Amp Class J fuse
OR
30Amp Class CC fuse
ul
UL - E116949, Vol. 2
When protected by;
60Amp Class J fuse
OR
30Amp Class CC fuse
ul
UL - E116949, Vol. 2
H12 Series 90A Solid-State Relays,
followed by D/CD/WD, followed by 4890
Additional Products Covered:
Series 1 (240/480Vac), H10, and HA/HD relays of the same ratings and construction are represented by Series H12.
H12WD4875 also represented in this categ
When protected by;
45Amp Class J fuse
OR
30Amp Class CC fuse
ul
UL - E116949, Vol. 2
When protected by;
100Amp Class J fuse
OR
30Amp Class CC fuse
ul
UL - E116949, Vol. 2
H12WD48125
Additional Products Covered:
H12D48125, H12CD48125, and CWA24125
When protected by;
50Amp Class J fuse
OR
30Amp Class CC fuse
ul
UL - E116950, Vol. 1
When protected by;
100Amp Class J fuse
OR
30Amp Class CC fuse
ul
UL - E116949, Vol. 1
DIN Rail SSR
CKRD6020
Additional Products Covered:
CKRD4820 and CKRD2420
When protected by;
20Amp Class J fuse
OR
20Amp Class CC fuse
ul
UL - E116950, Vol. 1
When protected by;
30Amp Class J fuse
OR
30Amp Class CC fuse
ul
UL - E116950, Vol. 1
CKRD6030
Additional Products Covered:
CKRD4830 and CKRD2430
When protected by;
30Amp Class J fuse
OR
30Amp Class CC fuse 
ul
UL - E116950, Vol. 1
When protected by;
30Amp Class J fuse
OR
30Amp Class CC fuse
ul
UL - E116950, Vol. 1
CMRD6035
Additional Products Covered:
CMRD4835 and CMRD2435
When protected by;
30Amp Class J fuse
OR
30Amp Class CC fuse   
ul
UL - E116950, Vol. 1
When protected by;
60Amp Class J fuse
OR
30Amp Class CC fuse
ul
UL - E116950, Vol. 1
CMRD6045
Additional Products Covered:
CMRD4845 and CMRD2445
When protected by;
45Amp Class J fuse
OR
30Amp Class CC fuse    
ul
UL - E116950, Vol. 1
When protected by;
60Amp Class J fuse
OR
30Amp Class CC fuse
ul
UL - E116950, Vol. 1
CMRD6055
Additional Products Covered:
CMRD4855 and CMRD2455
When protected by;
45Amp Class J fuse
OR
30Amp Class CC fuse    
ul
UL - E116950, Vol. 1
When protected by;
60Amp Class J fuse
OR
30Amp Class CC fuse
ul
UL - E116950, Vol. 1
CMRD6065
Additional Products Covered:
CMRD4865 and CMRD2465
When protected by;
60Amp Class J fuse
OR
30Amp Class CC fuse   
ul
UL - E116950, Vol. 1
When protected by;
100Amp Class J fuse
OR
30Amp Class CC fuse
ul
UL - E116950, Vol. 1
Dual SSR
H12D4825D
Additional Products Covered:
D2425D
When protected by;
20Amp Class J fuse
OR
20Amp Class CC fuse  
ul
UL - E116949, Vol. 2
When protected by;
30Amp Class J fuse
OR
30Amp Class CC fuse
ul
UL - E116949, Vol. 2
H12D4840D
Additional Products Covered:
D2440D
When protected by;
30Amp Class J fuse
OR
30Amp Class CC fuse    
ul
UL - E116949, Vol. 2
When protected by;
60Amp Class J fuse
OR
30Amp Class CC fuse

ul
UL - E116949, Vol. 2

*Notes regarding listed SCCR

Updated as of October 22, 2007
Models with lower voltage ratings are also represented
Models using suffixes are also represented
Class CC fuses are commercially available up to 30A only
Actual copy of certificate can be provided by request

Click here to download PDF