español english français italiano deutsch 中文
Return to Homepage Product Solutions Sales Support Contact Us About Us

 
Tech Tips
  How to test an AC Solid State Relay
For additional information:

AMERICAS

United States and Canada
2320 Paseo de las Americas,
Suite 201, San Diego, CA 92154
sales@crydom.com

Sales Support: (877) 502 5500
Technical Support: (877) 702 7700
Fax (619) 710 8540

Mexico
Tel: +52 (222) 409 7000
Fax: +52 (222) 409 7810

South America
Tel: +55 (11) 3026 9008
Fax: +55 (11) 3026 9009

EUROPE

United Kingdom
Tel: +44 (0) 1202 606030

Fax: +44 (0) 1202 606035

Germany
Tel: +49 (0) 180 3000 506

Italy
Tel: +39 02 66599260
Fax: +39 02 66599268

France
Tel: 0 810 123 963
Fax: 0 810 057 605

ASIA

China
Tel: +86 (21) 6249 0910
Fax: +86 (21) 6249 0701

Taiwan
Tel: +886 2 8751 6388 x130
Fax: +886 2 2657 8725

India
Tel: +91 (80) 329 02 245
Fax: +91 (80) 412 38 066

OTHER REGIONS

Tel: +44 (0) 1202 606030
Fax: +44 (0) 1202 606035

HOW TO TEST A SOLID STATE RELAY

There’s a very simple way to test an AC Solid State Relay. All you need is a 9 volt battery, a 40-100 Watt light bulb, and an AC source (your wall outlet will be it).

Figure 1 shows the way these devices should be connected. The DC control voltage will be your 9-volt battery with “+” connected to terminal 3 and “-“ connected to terminal 4.On the load side (terminals 1 and 2) you will have your light bulb (load) with one terminal connected to one side of the AC source (wall outlet) and the other terminal connected to terminal 2 of the relay (it can be connected to terminal 1 as they are electrically equivalent). The other wire of your AC source should be connected to terminal 1 of the relay to close the circuit.

When this is connected, the battery should control when the light is on or off. Applying the 9 volts DC will turn the light on and when you remove the DC voltage, the light bulb should turn-off.

If this does not occur, then, there’s a very high probability that you have a damaged relay.

Note: Using a voltmeter to test an SSR is not recommended because the voltage and current needed to trigger the output of an SSR are not present and therefore, producing erroneous readings.

For AC controlled relays the same applies, except that the control voltage will be AC instead of DC. The following figure shows a typical test setup for testing these relays.

When the switch is open, the light should be off, and with the switch closed, the light should be on. Anything else will indicate a faulty relay.